Well 5 - Kern Creek Well Active, 10 HP, 55 GPM, 350’, 7” Plastic Casing to 160’, pump at 336’, Drilled 1986 The well is drilled to 403’ The pump was replaced at least once due to failure. The well has a magnetic starter that protects from only from overload only. Caution this is a 240 Volt 3-phase system with a stinger leg! The well is configured for automated operation, but not connected or operated as such.